DIRIS A60 - Ref.: 536 418 A GB
DEFINITION OF THE FUNCTIONS OF VOLTAGE DIPS AND INTERRUPTION,
AS WELL AS VOLTAGE SWELL AND OVER-CURRENTS
DIRIS A60 allows detecting events such as:
• Voltage dips
• Voltage swells
• Interruption
• Over-currents
A packet of 10 RMS ½ period curves (I1, I2, I2, V1,
V2, V3, U12, U23, U31) is associated with each event
detected.
An RMS ½ curve period is made up of 120 points. For
a signal at 50 Hz it represents a history on 1.2s (60 Hz
for 1s ). A configurable trigger (Pre-post mode from
0 to 100 %) allows distributing the number of points
around the event (50% / 50% = 60 points before the
event and 60 points after).
For voltage dips, swells and over-currents, an event
starts if one of the quantities exceeds the determined
threshold. It ends if all the quantities have come back
to normal condition. (hysteresis).
For voltage interruption, an event starts if all the quan-
tities exceed the determined threshold. It ends if one of
the quantities has come back to normal condition.
Depending upon the length, the events are recorded
in the following manner:
Event < 1.2s (50 Hz), 1 packet of 10 curves over
1.2s.
1,2s > Event < 2.4s (50 Hz), 2 packets fol-
lowing 10 curves, i.e. 2.4s.
Event > 2.4s (50 Hz), 1 packet of 10 curves
consisting of the beginning of the event, 1
packet of 10 curves consisting of the end of
the event.
Between these two, the values are not availa-
ble.
>
Voltage dips and swells
They are memorized as per IEC 61000-4-30 and
EN50160 with a category B measurement method.
>
Voltage interruption
It is possible to configure the outage threshold (in %
of Un), on the other hand the measurement limit of
DIRIS A60 which is 29 V AC neutral phase and 50 V
AC phase/phase must be taken into account.
>
Over-currents
The detection threshold is configured in % of the CT
rating. Detection is made as in the case of voltage
swell.
DIRIS A60
PROGRAMMING
Ureg = 400V
EVENT
Recording of 1,2s
St
a
rt
End
50% 50%
Hysteresis = 380V
Threshold = 360V
U12
t
Example : Voltage dips with a 90 % voltage threshold and 5% hysteresis.