Primare A60 User Manual Page 53

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 52
53
DIRIS A60 - Ref.: 536 418 A GB
DIRIS A60
CARACTÉRISTIQUES TECHNIQUES
CASE
Dimensions: 97 x 97 x 80 mm
97 x 97 x 80 mm
with all optional modules (DIN 43700)
Connection: via 2.5 mm
2
disconnectable terminals
(voltage and others) and 6 mm
2
fixed terminals (current)
IP index: IP52 (front panel) and IP30 (case)
Weight: 465 gr.
DISPLAY
Type : Backlit LCD display
MEASUREMENTS
Three-phase (3 or 4 wires), two-phase (2 wire) and single-phase networks
VOLTAGE (TRMS)
Direct measurement: from 50 to 690 V AC (phase/phase)
from 28 to 400 V AC (phase/neutral)
Measurement via PT:
• Primary: up to 500 kV
• Secondary: 60, 100, 110, 115, 120, 173 and 190 V AC
Display and resolution from 0 to 500.0 kV
Permanent overload: 760 V AC
Update period: 1 second
CURRENT (TRMS)
Via CT with: • Primary: up to 10000 A
• Secondary: 1 or 5 A
Minimum measuring current 3mA with U ( Ph/N ) > 28 VAC
Input consumption: < 0.3 VA
Display: from 0 to 11 kA (1.1 times the primary value)
permanent overload: 10 A
intermittent overload: 10 In / 1 second
Update period: 1 second
Maximum ratio KI x KU: 10 000 000
POWER
Total: 0 to 8000 MW/Mvar/MVA
Update period: 1 second
FREQUENCY
from 45,0 to 65,0 Hz
Update period: 1 second
PULSE INPUT
110 to 400 V AC 50/60 Hz ± 10 %
120 to 350 V DC ± 20 %
12 to 48 V DC -6% / + 20 %
Consumption : < 10 VA
ALIMENTATION AUXILIAIRE IEC / CE
Forward voltage max. 30 V DC
Forward voltage min. 10 V DC
Reverse voltage max. 30 V DC
Galvanic insulation 3 kV
Minimum pulse width 1s
Max number of manoeuvres 10
8
Page view 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 59 60

Comments to this Manuals

No comments